Type RB-3P521LC
|
|
|
|
Best Suited as Control Relays where High Reliability is Required
For Steel Plant Equipment, Electric Utilities, Transit Vehicles and Low Level Signals under Severe Operating Conditions.
Features
- Excellent performance provided when used for DC solenoid valves and solenoid loads. Without protective circuit components, 1,000,000 operations at 50W load can be ensured.
- Maximum reliability can be assured in non- frequent operation.
- Direct DC control from 1V 1mA on up to 230VAC.
- The hermetically sealed contact design prevents the contacts from deteriorating even in a corrosive environment.
- Mechanical failure should not occur since no moving parts such as an armature are included.
- Applicable at different voltage levels.
- AC actuated types available on order.
- Type RB-3P Recognized in accordance with USA and Canadian standards File No. E154773. For Class I, Division 2 Groups A,B,C,D Hazardous Locations.
Typical Applications
- Auxiliary sequence
- Emergency interlock
- For DC solenoid load controlling (Especially 100VDC or greater)
- For adverse atmosphere
- For vehicles
- For signals
- For elevators
|
|
|
|
Contact Arrangement
|
|
2NO1NC
|
|
Operational Power Ratings (lnductive Load) 1
|
|
240VAC 1A, 230VDC 0.2A, 115VDC 0.5A
|
|
Min. Operational Power Ratings
|
|
1V 1mA (for R14), 24 V 1 mA (for R15)
|
|
Operating Time2
|
|
40 ms or less (with overlap)
|
|
Releasing Time 3
|
|
40 ms or less (with overlap)
|
|
Vibration Resistance4
|
|
44.1 m/s2 (4.5G) or greater (0 to 55Hz)
|
|
Shock Resistance -- Erroneous Operation
|
|
147.0m/s2 [15G]
|
|
Shock Resistance -- Breakdown
|
|
490.0m/s2 [50G] or greater
|
|
Withstand Voltage
|
|
2000VAC for 1 minute (across contacts: 800 VAC)
|
|
Approx. Weight
|
|
120g
|
|
Incorporated Bestact Type (Item Type)
|
|
R15, Large-Capacity (For heavy duty)
|
|
1 For details of contact ratings, life, characteristics, etc., refer to the Ratings, Specilications. and Electrical Life
2 Operating and releasing time are the values at rated voltage (20"C). Each of NO and NC contact operates independently. Therefore, the operating time of NO contact and NC contact may overlap.
3 Operating and releasing time are the values at rated voltage (20"C). Each of NO and NC contact operates independently. Therefore, the operating time of NO contact and NC contact may overlap.
4 Values of vibration/shock resistance are obtained when Bestact is equipped with relay retaining band.
|
|
|
|
|
|
|
|
|
|
|
|
|